Rule 217.283 Post-disinfection Requirements

(a) Sampling points must be identified in the engineering report. A design must include a sufficient number of sampling points to: (1) allow an operator to monitor the disinfection system for process control; and (2) allow monitoring of permitted effluent limits. (b) Dissolved Oxygen Requirements. A treatment facility must be designed with the ability to add post-aeration if needed to meet effluent limits for dissolved oxygen in the wastewater permit. If the wastewater permit requires a minimum dissolved oxygen of 5.0 milligrams per liter or greater, the engineering report must include calculations that demonstrate how the post-aeration system will maintain the minimum dissolved oxygen level. Source Note: The provisions of this §217.283 adopted to be effective August 28, 2008, 33 TexReg 6843; amended to be effective December 4, 2015, 40 TexReg 8254
Gavvy last updated this database on: Aug 7, 2024