(a) The emission limits of this division apply at all times except during periods of municipal waste combustion unit startup, shutdown, or malfunction.
(b) Each startup, shutdown, or malfunction must not last for longer than 3 hours.
(c) A maximum of 3 hours of test data can be dismissed from compliance calculations during periods of startup, shutdown, or malfunction.
(d) During startup, shutdown, or malfunction periods longer than 3 hours, emissions data cannot be discarded from compliance calculations and all provisions under 40 Code of Federal Regulations §60.11(d) apply.
Source Note: The provisions of this §113.2126 adopted to be effective May 14, 2009, 34 TexReg 2771